RCCB DIN-SAFE 1P+N 40A 30mA TYPE F

Item No. DSRCD24030F
RCCB DIN-SAFE 1P+N 40A 30mA TYPE F
This product cannot be ordered at the moment.
Indent item (non-returnable)
Description
RCCB DIN-SAFE 1P+N 40A 30mA TYPE F
Specifications
Brand Name NHP Din-T
L03 Name (Fam) Miniature Circuit Breakers and Earth Leakage Protection (RCDs and RCBOs)
Standards Compliance AS/NZS 61008 EN 61008-1 IEC 61008-1
Certifications CE RCM
Add-On Devices (side add-on) Auxiliary Contacts PBS Tele L Tele M Tele U
Component Type Power Distribution & Protection RCD
Number of Poles versus Modules 1
Tripping Time at IΔn, Instantaneous <300
Tripping Time at IΔn, Selective >150
Approval(s) N17482
Busbar System, Bottom Fork Pin
Busbar System, Top Fork Pin
IΔn, Rated Leakage Current 30
Im, Rated Make/Break Capacity 500
IΔm, Rated Residual Make/Break Capacity 500
In, Rated Current at 30°C 40
Inc, Rated Conditional Short Circuit Current 10
IΔc, Rated Conditional Residual Short-Circuit Current 10000
Depth 76
Dielectric Strength 2500V
Grid Distance (Safety Difference Between 2 Devices) 35
Rated Frequency 50 / 60 Hz
Height 86
Relative Humidity, Max 95
IP Rating, Inside IP40
IP Rating, Outside IP20
Mounting DIN-35 Rail Mount
Package Quantity 3
Padlockable Yes, Non-Captive only (Ordered Separately)
Poles 1P + N
Conductor Entry Position Top / Bottom
Flammability Rating (UL94) UL 94 V-2
Shock Rating IEC 60077-16-3
Vibration Rating IEC 60068-2-6
Insulation Resistance 1000
Supplier Declaration of Conformity DSRCDxxxxxx_Supplier Declaration of Conformity (SDoC)
Electrical Service Life at Un, In 10000
Mechanical service life 20000
Shock Acceleration (Max.) 40
Shock Duration (Max.) 5
Operating Temperature, Max 55
Operating Temperature, Min -25
Storage Temperature, Max 70
Storage Temperature, Min -25
Tightening Torque, Bottom, Nominal 5
Tightening Torque, Top, Nominal 5
RCD Type, AS/NZS 61008/61009 F
Vibration Acceleration (Max.) 1.5
Vibration Duration (Max.) 30
Vibration Frequency, Operational (Max.) 80
Uimp, Impulse Withstand Voltage, 1.2/50µs 8
Impulse Withstand Test Voltage 6
Ui, Rated Insulation Voltage 440
Un, Nominal Operational Voltage, AC 415
Ubmax, Service Voltage, AC, Max 265
Ubmin, Service Voltage, AC, Min 117
Weight 0.368
Width 36
Wire / Conductor Size, Flex Cable, Bottom, Max 35 mm²
Wire / Conductor Size, Flex Cable, In, Min 1.5 mm²
Wire / Conductor Size, Flex Cable, Out, Min 1.5 mm²
Wire / Conductor Size, Flex Cable, Top, Max 35 mm²
Wire / Conductor Size, Rigid Cable, Bottom, Max 50 mm²
Wire / Conductor Size, Rigid Cable, In, Min 1.5 mm²
Wire / Conductor Size, Rigid Cable, Out, Min 1.5 mm²
Wire / Conductor Size, Rigid Cable, Top, Max 50 mm²
Isolator Application, IEC 60947-2 Yes
Neutral Pole Protected Yes
Sealable Yes
Trip-Free Mechanism Yes
Centre Trip Position No
Features and Benefits
  • DIN rail mounting
  • Free tripping mechanism even if toggle is locked or sealed ON or OFF
    Loading